Case: T07FR00204
Case Details
Entered Date:
01/29/2007
Applicant:
DHS PROPERTY INVESTMENTS LTD PARTNERSHIP
Description:
Full Fire Inspection
Outstanding Inspections
Case Number: T07FR00204
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
INSP - FULL | None | Not Inspected | ||
01/22/2007 | VIOL - FIRE RESIST.RATED CONST | NSPRENGE | Violation | 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Replace ceiling tile in communications room. |
01/22/2007 | VIOL - FIRE PROTECTION SYSTEMS | NSPRENGE | Violation | 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. Have your fire extinguishers serviced/tested. |