Case: T07FR00198
Case Details
Entered Date:
01/26/2007
Applicant:
DND NEFFSON CO
Description:
Full fire inspection done by Inspector John Bieg 1-26-07.
Outstanding Inspections
Case Number: T07FR00198
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/26/2007 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.3 Remove storage from blocking electrical service equipment. A re-inspection is scheduled for 2-9-07. |
01/26/2007 | VIOL - INT.FINISH, DEC. MATL'S | JBURGE | Correction Required | TFC 803.1.3 Remove merchandise from obstructing the rear exit sign. |
01/26/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6 Service and tag the fire extinguisher, by entrance to back room. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR00198
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/20/2007 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations were corrected on 2-16-07. Inspector John Bieg. |