Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

01/24/2007

Applicant:

DND NEFFSON CO

Description:

Full inspection done by Inspector John Bieg 1-24-07.

Outstanding Inspections

Case Number: T07FR00187
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
01/24/2007 VIOL - FIRE RESIST.RATED CONST JBURGE Correction Required TFC 703.1 Replace all missing ceiling tiles, in back rooms. A re-inspection is scheduled for 2-7-07.
01/24/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1011.2 Exit sign over the front entrance shall be illuminated.
01/24/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1026.5 The exit sign in the shoe stock room shall have smergency back-up power.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR00187
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
02/08/2007 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected on 2-7-07. Inspector John Bieg.