Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

01/23/2007

Applicant:

DND NEFFSON CO

Description:

Full fire inspection done by Inspector John Bieg 1-22-07.

Outstanding Inspections

Case Number: T07FR00180
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
01/23/2007 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required TFC 315.2 Rear storage rooms shall comply with this code. A re-inspection is scheduled for 2-8-07.
01/23/2007 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required TFC 315.2.1 Rear storage area shall comply with this code.
01/23/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.3 Remove storage from blocking electrical service equipment in the back room.
01/23/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 906.7 Mount extinguisher in the south east exit corridor.
01/23/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1011.2 Exit signs and emergency lighting in the southeast exit and exit access shall be illuminated.
01/23/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.2 #1. Remove storage from the southeast exit and exit corridor. #2. Remove storage from the northeast exit access.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR00180
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
02/13/2007 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were correcterd on 2-8-07. Inspector John Bieg.