Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

01/18/2007

Applicant:

DND NEFFSON CO

Description:

Full fire inspection done by Inspector John Bieg 1-18-07.

Outstanding Inspections

Case Number: T07FR00164
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
01/18/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space. 1. Remove storage from blocking electrical service equipment, in back room.
01/18/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Non required fire protection systems and equipment shall be inspected, tested and maintained or removed. 1. Service and tag extinguisher in back room. Call me if you have any questions at 791-4014, Ext.122.
01/18/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions. 1. Mount extinguisher in back room.
01/18/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1026.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system for the following occupancies where such occupancies require two or more means of egress: 1. Repair emergency lighting over rear exit.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR00164
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
02/21/2007 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations were corrected on 2-20-07. Inspector John Bieg.