Case Number: T07FR00150
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
01/18/2007 VIOL - ADMINISTRATION NSPRENGE Violation [EB] 102.3 Change of use or occupancy. The provisions of the International Existing Building Code shall apply to all buildings undergoing a change of occupancy. Apply for a certificate of occupancy at Developmental Services Department ( 201 N Stone).
01/18/2007 VIOL - PRECAUTION AGAINST FIRE NSPRENGE Violation 315.2.1 Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. Maintain 18 inches clearance below sprinkler head in copier room.
01/18/2007 VIOL - BUILDING SVCS & SYSTEMS NSPRENGE Violation 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space. Remove picture from covering the electric panel in Scott's office and maintain clearances.
01/18/2007 VIOL - BUILDING SVCS & SYSTEMS NSPRENGE Violation 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. Replace missing outlet faceplates in Becky's office and in communications closet.