Case: T07FR00145
Case Details
Entered Date:
01/18/2007
Applicant:
DHS PROPERTY INVESTMENTS LTD PARTNERSHIP
Description:
Full Inspection
Outstanding Inspections
Case Number: T07FR00145
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
INSP - FULL | None | Not Inspected | ||
01/18/2007 | VIOL - BUILDING SVCS & SYSTEMS | NSPRENGE | Violation | 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. Remove two extension cords in offices. |
01/18/2007 | VIOL - MEANS OF EGRESS | NSPRENGE | Violation | 1011.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in an exit access corridor is more than 100 feet (30 480 mm) or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. Provide illuminated exit sign - visible from all directions - leading to exit stairwell. |