Description:

Full fire inspection done by Inspector John Bieg 1-17-07.

Outstanding Inspections

Case Number: T07FR00138
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
01/17/2007 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required TFC 315.2.1 Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. 1. Remove storage from blocking the sprinkler head in the closet behind the register.
01/17/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space. 1. Remove storage from blocking electrical service equipment.
01/17/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Non required fire protection systems and equipment shall be inspected, tested and maintained or removed. 1. Service and tag extinguisher behind the register. 2. Service and tag 2 extinguishers in back stock room.
01/17/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions. 1. Mount extinguisher in back stock room.
01/17/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1026.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system for the following occupancies where such occupancies require two or more means of egress: 1. Exit sign leading to rear exit shall have emergency back-up power.
01/17/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency. Security devices affecting means of egress shall be subject to approval of the fire code official. 1. Remove storage from blocking the rear exit.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR00138
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
02/05/2007 INSP - FULL JBURGE Approved All Tucson Fire Code violations were corrected on 2-2-07. Inspector John Bieg.