Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

01/16/2007

Applicant:

DHS PROPERTY INVESTMENTS LTD PARTNERSHIP

Description:

Full Fire Inspection

Outstanding Inspections

Case Number: T07FR00119
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
01/16/2007 INSP - FULL NSPRENGE Correction Required
01/16/2007 VIOL - ADMINISTRATION NSPRENGE Violation [EB] 102.3 Change of use or occupancy. The provisions of the International Existing Building Code shall apply to all buildings undergoing a change of occupancy. Apply for a certificate of occupancy at Developmental Services Department ( 210 N Stone).
01/16/2007 VIOL - BUILDING SVCS & SYSTEMS NSPRENGE Violation 605.4.2 Power supply. Relocatable power taps shall be directly connected to a permanently installed receptacle. Unplug from each other the 'piggybacked' powerstrips and connect to a permanent receptacle.
01/16/2007 VIOL - BUILDING SVCS & SYSTEMS NSPRENGE Violation Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. Remove extension cord in Matt's office.
01/16/2007 VIOL - MEANS OF EGRESS NSPRENGE Violation 1011.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Place 3 exit signs to meet requirements of signs being visible from all directions. The main exit is distinguishable and does not require a sign per IFC 1011.1 exception #2.
01/16/2007 VIOL - MEANS OF EGRESS NSPRENGE Violation 1011.2 Illumination. Exit signs shall be internally or externally illuminated. Cause your exit sign to be illuminated with a back-up battery in case of electrical failure.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR00119
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
02/16/2007 COMPL - REINSPECTION NSPRENGE Approved