Case: T07FR00119
Case Details
Entered Date:
01/16/2007
Applicant:
DHS PROPERTY INVESTMENTS LTD PARTNERSHIP
Description:
Full Fire Inspection
Outstanding Inspections
Case Number: T07FR00119
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/16/2007 | INSP - FULL | NSPRENGE | Correction Required | |
01/16/2007 | VIOL - ADMINISTRATION | NSPRENGE | Violation | [EB] 102.3 Change of use or occupancy. The provisions of the International Existing Building Code shall apply to all buildings undergoing a change of occupancy. Apply for a certificate of occupancy at Developmental Services Department ( 210 N Stone). |
01/16/2007 | VIOL - BUILDING SVCS & SYSTEMS | NSPRENGE | Violation | 605.4.2 Power supply. Relocatable power taps shall be directly connected to a permanently installed receptacle. Unplug from each other the 'piggybacked' powerstrips and connect to a permanent receptacle. |
01/16/2007 | VIOL - BUILDING SVCS & SYSTEMS | NSPRENGE | Violation | Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. Remove extension cord in Matt's office. |
01/16/2007 | VIOL - MEANS OF EGRESS | NSPRENGE | Violation | 1011.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Place 3 exit signs to meet requirements of signs being visible from all directions. The main exit is distinguishable and does not require a sign per IFC 1011.1 exception #2. |
01/16/2007 | VIOL - MEANS OF EGRESS | NSPRENGE | Violation | 1011.2 Illumination. Exit signs shall be internally or externally illuminated. Cause your exit sign to be illuminated with a back-up battery in case of electrical failure. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR00119
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/16/2007 | COMPL - REINSPECTION | NSPRENGE | Approved |