Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

01/16/2007

Applicant:

INTERGALECTIC PROPERTIES LLC

Description:

Full Inspection

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR00116
Case Description: INSPECTION
Total Completed Inspections - 8
End Date Description Inspector Results Comments
01/11/2007 VIOL - FIRE PROTECTION SYSTEMS DRAMIREZ Approved TFC 907.2.6.2.3 Smoke detectors randomly tested, malfunctioned. You shall provide documentation indicating the testing and proper functioning of every smoke detector in the hotel.
01/11/2007 VIOL - FIRE RESIST.RATED CONST DRAMIREZ Approved TFC 703.1 Openings in walls and ceilings shall be protected from passage of smoke and fire. 1.) kitchen area behind door in corridor. 2.) next to water heater. 3.) storage closet next to ice machine, 1st. flr.
01/11/2007 VIOL - BUILDING SVCS & SYSTEMS DRAMIREZ Approved TFC 605.3 Provide a clear working space around electrical panel. 1.) storage area, tables and chairs in front of panel. 2.) main electrical panel
01/11/2007 VIOL - BUILDING SVCS & SYSTEMS DRAMIREZ Approved TFC 605.6 Provide covers for electrical boxes. 1.) kitchen area. 2.) electrical panel, kitchen area.
01/11/2007 VIOL - MEANS OF EGRESS DRAMIREZ Approved TFC 1008.1.8.4 You shall remove pad lock from rear exit door. Kitchen area.
01/11/2007 VIOL - MEANS OF EGRESS DRAMIREZ Approved TFC 1006.3 Emergency back-up lighting shall be provided. 1.) kitchen area, exit access crridor. 2.) bar area.
01/11/2007 VIOL - MEANS OF EGRESS DRAMIREZ Approved TFC 1011.2 Exit signs shall be illuminated. 1.) Front lobby, main exit. 2.) east exit, to to pool area. 3.) kitchen exit. 4.) bar room area.
01/11/2007 INSP - FULL DRAMIREZ Approved