Case: T07FR00116
Case Details
Entered Date:
01/16/2007
Applicant:
INTERGALECTIC PROPERTIES LLC
Description:
Full Inspection
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR00116
Case Description: INSPECTION
Total Completed Inspections - 8
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/11/2007 | VIOL - FIRE PROTECTION SYSTEMS | DRAMIREZ | Approved | TFC 907.2.6.2.3 Smoke detectors randomly tested, malfunctioned. You shall provide documentation indicating the testing and proper functioning of every smoke detector in the hotel. |
| 01/11/2007 | VIOL - FIRE RESIST.RATED CONST | DRAMIREZ | Approved | TFC 703.1 Openings in walls and ceilings shall be protected from passage of smoke and fire. 1.) kitchen area behind door in corridor. 2.) next to water heater. 3.) storage closet next to ice machine, 1st. flr. |
| 01/11/2007 | VIOL - BUILDING SVCS & SYSTEMS | DRAMIREZ | Approved | TFC 605.3 Provide a clear working space around electrical panel. 1.) storage area, tables and chairs in front of panel. 2.) main electrical panel |
| 01/11/2007 | VIOL - BUILDING SVCS & SYSTEMS | DRAMIREZ | Approved | TFC 605.6 Provide covers for electrical boxes. 1.) kitchen area. 2.) electrical panel, kitchen area. |
| 01/11/2007 | VIOL - MEANS OF EGRESS | DRAMIREZ | Approved | TFC 1008.1.8.4 You shall remove pad lock from rear exit door. Kitchen area. |
| 01/11/2007 | VIOL - MEANS OF EGRESS | DRAMIREZ | Approved | TFC 1006.3 Emergency back-up lighting shall be provided. 1.) kitchen area, exit access crridor. 2.) bar area. |
| 01/11/2007 | VIOL - MEANS OF EGRESS | DRAMIREZ | Approved | TFC 1011.2 Exit signs shall be illuminated. 1.) Front lobby, main exit. 2.) east exit, to to pool area. 3.) kitchen exit. 4.) bar room area. |
| 01/11/2007 | INSP - FULL | DRAMIREZ | Approved |