Case: T07FR00104
Case Details
Entered Date:
01/16/2007
Applicant:
DND NEFFSON CO
Description:
Full fire inspection done by Inspector John Bieg 1-12-07.
Outstanding Inspections
Case Number: T07FR00104
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/16/2007 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.3 Remove storage from blocking electrical storage equipment. In electrical room. |
01/16/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6 Comply with the following code. Extinguisher in rear exit corridor. A re-inspection is scheduled for 1-26-07. |
01/16/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 906.6 Comply with the following code. Extinguisher in rear exit corridor. |
01/16/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1011.2 Exit signs shall be illuminated by battery back up power. Exit corridor, exit sign in rear. |
01/16/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.2 Remove storage from exit access. Rear exit. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR00104
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/05/2007 | INSP - FULL | JBURGE | Approved | All Tucson Fire Code violations were corrected on 2-2-07. Inspector John Bieg. |