Case: T07FR00090
Case Details
Entered Date:
01/11/2007
Applicant:
CAMPBELL/GRANT JOINT VENTURE LLC
Description:
Full Inspection
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR00090
Case Description: INSPECTION
Total Completed Inspections - 8
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/26/2006 | VIOL - FIRE PROTECTION SYSTEMS | DRAMIREZ | Approved | TFC 901.6 Non required fire protection systems and equipment shall be inspected, tested and maintained or removed. |
12/26/2006 | VIOL - MEANS OF EGRESS | DRAMIREZ | Approved | TFC 1019.1.5 Storage of combustible material under unenclosed stairway is prohibited. |
12/26/2006 | VIOL - MEANS OF EGRESS | DRAMIREZ | Approved | TFC 1027.2 Exits shall be free from obstrutions. |
12/26/2006 | VIOL - BUILDING SVCS & SYSTEMS | DRAMIREZ | Approved | TFC 605.3.1 Door to electrical room shall be labled, "ELECTRICAL ROOM" |
12/26/2006 | VIOL - BUILDING SVCS & SYSTEMS | DRAMIREZ | Approved | TFC 605.4.1 Power taps shall be polarized or grounded type, equipped with overcurrent protection.Power taps shall be directly connected to a permanently installed receptical. |
12/26/2006 | VIOL - BUILDING SVCS & SYSTEMS | DRAMIREZ | Approved | TFC 605.1 Electrical wiring supplying power to the video games shall be from a permanently installed source and shall be installed in accordance to the electrical code or supplied by approved relocatable power taps. |
12/26/2006 | VIOL - BUILDING SVCS & SYSTEMS | DRAMIREZ | Approved | TFC 605.5 Extension cords shall not be used as permanent wiring. Extension cords shall not be extended under floor coverings.(Including duct tape) |
12/26/2006 | INSP - FULL | DRAMIREZ | Approved |