Case: T07FR00067
Case Details
Entered Date:
01/10/2007
Applicant:
DND NEFFSON CO
Description:
Full Fire inspection done by Inspector John Bieg 1-8-07.
Outstanding Inspections
Case Number: T07FR00067
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/10/2007 | VIOL - PRECAUTION AGAINST FIRE | JBURGE | Correction Required | TFC 315.2.1. Remove storage from blocking sprinkler heads, {break room north wall}. A re-inspection is scheduled for 1-22-07. |
01/10/2007 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.3. Remove storage from blocking electrical pannels in employee break room. |
01/10/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1011.2. #1. Exit sign shall be illuminated, {southeast exit door}. #2. Exit signs shall be illuminated, {signs in exit access, southwest side by the register}. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR00067
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/23/2007 | INSP - FULL | JBURGE | Approved | All Tucson Fire Code violations were corrected 1-22-07. Inspector John Bieg. |