Case: T07FR00026
Case Details
Entered Date:
01/04/2007
Applicant:
HOLMES TUTTLE FORD
Description:
Complaint follow-up
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR00026
Case Description: INSPECTION
Total Completed Inspections - 11
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/07/2006 | VIOL - PRECAUTION AGAINST FIRE | DRAMIREZ | Approved | TFC 315.2 Storage shall be maintained 18 inches minimum below sprinkler head deflectors. |
08/07/2006 | VIOL - MEANS OF EGRESS | DRAMIREZ | Approved | TFC 901.6.2 Records of all systems inspections. tests and maintenance for the previous 3 years minimum, shall be on the premises and be made available upon request. |
08/07/2006 | VIOL - MEANS OF EGRESS | DRAMIREZ | Approved | TFC 901.6 Fire protection system is required to be inspected, tested and maintained annually. Sprinkler system inspection is past due. |
08/07/2006 | VIOL - MEANS OF EGRESS | DRAMIREZ | Approved | TFC 1011.1 Shall provide an illuminated exit sign for door leading from "stockroom" to "showroom". |
08/07/2006 | VIOL - MEANS OF EGRESS | DRAMIREZ | Approved | TFC 1011.2 Exit signs shall be illuminated at all times. 1.) Showroom, 2 doors. 2.) Service enterance. 3.) Parts showroom, east exit door. 4.) Dispatchaera. |
08/07/2006 | VIOL - FIRE RESIST.RATED CONST | DRAMIREZ | Approved | TFC 703.1 Openings in ceiling or walls shall be properly repaired to resist the passage of smoke or fire. 1.) ceiling, main showroom. 2.) wall, electrical room. 3.) ceiling, mechanical room. 4.) wall, office, 2nd. level. |
08/07/2006 | VIOL - BUILDING SVCS & SYSTEMS | DRAMIREZ | Approved | TFC 605.3.1 Door for electrical room and mechanical room shall be labled: ELECTRICAL ROOM and MECHANICAL ROOM. |
08/07/2006 | VIOL - BUILDING SVCS & SYSTEMS | DRAMIREZ | Approved | TFC 605.4.2 Relocatable power taps shall be the polarized or grounded type, equipped with overcurrent protection and shall be directly connected to a permanently installed recepticle.(no piggy-backing) |
08/07/2006 | VIOL - BUILDING SVCS & SYSTEMS | DRAMIREZ | Approved | TFC 605.5 Extension cords shall not be a substitue for permanent wiring. |
08/07/2006 | VIOL - BUILDING SVCS & SYSTEMS | DRAMIREZ | Approved | TFC 605.4 Multiplug adaptors such as cubed adaptors shall be prohibited. |
08/07/2006 | INSP - FULL | DRAMIREZ | Approved | Refer to T0 numbers T07FR00003 to 00007. |