Description:

Complaint follow-up

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR00026
Case Description: INSPECTION
Total Completed Inspections - 11
End Date Description Inspector Results Comments
08/07/2006 VIOL - PRECAUTION AGAINST FIRE DRAMIREZ Approved TFC 315.2 Storage shall be maintained 18 inches minimum below sprinkler head deflectors.
08/07/2006 VIOL - MEANS OF EGRESS DRAMIREZ Approved TFC 901.6.2 Records of all systems inspections. tests and maintenance for the previous 3 years minimum, shall be on the premises and be made available upon request.
08/07/2006 VIOL - MEANS OF EGRESS DRAMIREZ Approved TFC 901.6 Fire protection system is required to be inspected, tested and maintained annually. Sprinkler system inspection is past due.
08/07/2006 VIOL - MEANS OF EGRESS DRAMIREZ Approved TFC 1011.1 Shall provide an illuminated exit sign for door leading from "stockroom" to "showroom".
08/07/2006 VIOL - MEANS OF EGRESS DRAMIREZ Approved TFC 1011.2 Exit signs shall be illuminated at all times. 1.) Showroom, 2 doors. 2.) Service enterance. 3.) Parts showroom, east exit door. 4.) Dispatchaera.
08/07/2006 VIOL - FIRE RESIST.RATED CONST DRAMIREZ Approved TFC 703.1 Openings in ceiling or walls shall be properly repaired to resist the passage of smoke or fire. 1.) ceiling, main showroom. 2.) wall, electrical room. 3.) ceiling, mechanical room. 4.) wall, office, 2nd. level.
08/07/2006 VIOL - BUILDING SVCS & SYSTEMS DRAMIREZ Approved TFC 605.3.1 Door for electrical room and mechanical room shall be labled: ELECTRICAL ROOM and MECHANICAL ROOM.
08/07/2006 VIOL - BUILDING SVCS & SYSTEMS DRAMIREZ Approved TFC 605.4.2 Relocatable power taps shall be the polarized or grounded type, equipped with overcurrent protection and shall be directly connected to a permanently installed recepticle.(no piggy-backing)
08/07/2006 VIOL - BUILDING SVCS & SYSTEMS DRAMIREZ Approved TFC 605.5 Extension cords shall not be a substitue for permanent wiring.
08/07/2006 VIOL - BUILDING SVCS & SYSTEMS DRAMIREZ Approved TFC 605.4 Multiplug adaptors such as cubed adaptors shall be prohibited.
08/07/2006 INSP - FULL DRAMIREZ Approved Refer to T0 numbers T07FR00003 to 00007.