Description:

full inspection

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR00022
Case Description: INSPECTION
Total Completed Inspections - 6
End Date Description Inspector Results Comments
08/15/2006 VIOL - BUILDING SVCS & SYSTEMS DRAMIREZ Approved TFC 605.3.1 Door to electrical equipment room shall be provided with a sign reading: "ELECTRICAL ROOM".
08/15/2006 VIOL - PRECAUTION AGAINST FIRE DRAMIREZ Approved TFC 315.2.1 Storage shall be maintained a minimum of 18 inches below a sprinkler deflector.
08/15/2006 VIOL - FIRE PROTECTION SYSTEMS DRAMIREZ Approved TFC 901.6.2 Records of fire protection maintanance, inspections, testing etc. shall be available on the premises.
08/15/2006 VIOL - MEANS OF EGRESS DRAMIREZ Approved TFC 1019.1.5 Storage of any combustable material under a stairway is prohibited.
08/15/2006 VIOL - MEANS OF EGRESS DRAMIREZ Approved TFC 1006.3 Repair emergency bakup light located over front desk in main lobby.
08/15/2006 INSP - FULL DRAMIREZ Approved