Case Status: COMPLETE
Case Number: T07FR00020
Case Description: INSPECTION
Total Completed Inspections - 6
End Date Description Inspector Results Comments
08/02/2006 VIOL - ADMINISTRATION DRAMIREZ Approved TFC 111.1 Two appliances under hood have been "Red Tagged" for non coverage by nozzles.
08/02/2006 VIOL - FIRE PROTECTION SYSTEMS DRAMIREZ Approved TFC904.11.5 Shall provide a K-rated fire extinguisher for the kitchen.
08/02/2006 VIOL - FIRE PROTECTION SYSTEMS DRAMIREZ Approved TFC 904.11.6 Shall have the nozzles of the hood system inspected for proper positioning and placement.
08/02/2006 VIOL - FIRE PROTECTION SYSTEMS DRAMIREZ Approved TFC 901.6 Nonrequired portable fire extinguishers shall be inspected,tested and maintained OR removed.
08/02/2006 VIOL - BUILDING SVCS & SYSTEMS DRAMIREZ Approved TFC 605.5 Approved cover boxes shall be provided for exposed electrical wiring in following areas: 1.) Kitchen area under counter. 2.) Next to freezer door. 3.) Inside freezer area, wiring to A/C unit. 4.) Main electrial panel next to rear exit, 5.) Exterior side of rear wall net to rear exit.
08/02/2006 INSP - FULL DRAMIREZ Approved