Case Details

Status:

COMPLIAN

Type:

RES: MINIMUM HOUSING

Entered Date:

01/26/2007

Applicant:

ICE NINE LLC

Description:

TENANT SAYS SHE HAS BEEN WITHOUT HEAT SINCE SHE MOVED IN TO HER HOME ON 12/15/06. LANDLORD PROVIDED HER WITH SOME SPACE HEATERS BUT IT IS NOT ENOUGH TO KEEP HER WARM.. LANDLORD THEN PROVIDED HER WITH A FURNACE THAT HER FRIEND WAS GOING TO INSTALL. THEY COULD NOT REMOVE OLD FURNACE BECAUSE IT WAS GOING TO CAUSE PROPERTY DAMAGE. SHE HAS NOT BEEN ABLE TO GET A HOLD OF THE LANDLORD. SHE ALSO ADDED THAT THE HOME IS INFESTED WITH ROACHES.

Outstanding Inspections

Case Number: T07DV00878
Case Status: COMPLIAN
Case Description: RES: MINIMUM HOUSING
Total Outstanding Inspections - 8
End Date Description Inspector Results Comments
INSP - FOLLOW UP CODE ENFORCE None Not Inspected
04/04/2008 VIOL(EL) - CIRCUITS RMENDOZA Item closed
04/04/2008 NPO(EL)-WIRING/SWITCH/OUTLT/FX RMENDOZA Item closed
04/04/2008 VIOL(PL) - FIXTURES RMENDOZA Item closed
04/04/2008 NPO(PL)-WATER HEATERS RMENDOZA Item closed
04/04/2008 NPO(HC)-HEATING & VENTILATION RMENDOZA Item closed
04/04/2008 VIOL(SA) - BATHS RMENDOZA Item closed
04/04/2008 NPO - SMOKE ALARMS RMENDOZA Item closed

Completed Inspections

Case Status: COMPLIAN
Case Number: T07DV00878
Case Description: RES: MINIMUM HOUSING
Total Completed Inspections - 1
End Date Description Inspector Results Comments
02/01/2007 INSP - INITIAL CODE ENFORCMENT RMENDOZA Approved DWELLING LACKS SMOKE DETECTORS DWELLING LACKS HEATING. SPACE HEATERS ARE BEING UTILIZED TO HEAT THE DWELLING. 220 VOLT ELECTRICAL OUTLET INSTALLED ON THE SOUTH WALL IN THE LIVING ROOM WITHOUT PERMITS. KITCHEN LACKS GFCI PROTECTION. KITCHEN AND BATH ELECTRICAL CIRCUITS APPEAR TO BE CONNECTED TO THE SAME BRANCH CIRCUIT. WASHING MACHINE WATER CONNECTION LEAKS. BATHTUB FAUCET LEAKS. WATER HEATER LACKS COLD WATER SHUT OFF. NO ACCESS TO GAS SHUT OFF. FLUE VENT PIPE IS NOT ATTACHED TO THE APPLIANCE. WATER HEATER CLOSET IS IN DISREPAIR. DOOR DOES NOT SHUT PROPERLY. PHOTOS TAKEN. RM

Completed Activity Special Conditions

Case Description - RES: MINIMUM HOUSING
Case Number - T07DV00878
Case Status: COMPLIAN
Total Completed Case Activity Conditions: 5
Date Name
11/02/2007 CONTACTED BY PHONE
06/28/2007 CONTACTED IN PERSON
02/06/2007 CONTACTED BY MAILING
04/14/2008 VIOLATION CLOSED
04/14/2008 RESEARCH

Documents

File Name Document Type  
None DOCUMENTS VIEW
None DOCUMENTS VIEW
None IMAGES VIEW