Full fire Inspection done by Inspector John Bieg, on 12-27-06, "M" occupancy.

Outstanding Inspections

Case Number: T06FR02934
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 10
End Date Description Inspector Results Comments
12/27/2006 INSP - FULL JBURGE Correction Required Please correct the following Tucson Fire Code Violations:
12/27/2006 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required TFC 315.2.1 Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. 1. Men's shoes stock room shall meet these requirements.
12/27/2006 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC 508.5.4 Obstruction. Posts, fences, vehicles, growth, trash, storage and other materials or objects shall not be placed or kept near fire hydrants, fire department inlet connections or fire protection system control valves in a manner thatwould prevent such equipment or fire hydrants from being immediately discernible. The fire department shall not be deterred or hindered from gaining immediate access to fire protection equipment or fire hydrants. 1. Remove bushes from blocking fire department sprinkler connection, on northeast exterior of building.
12/27/2006 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. 1. Remove storage from around florescent lights, in china stock room.
12/27/2006 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. 1. Clear area in front of electrical panel in an approved manner. Recieving dock bailer disconnect blocked. 2. Remove storage in front of electrical panels, in houseware stock room.
12/27/2006 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.4.2 Power supply. Relocatable power taps shall be directly connected to a permanently installed receptacle. 1. Remove noncomplying devices. Giftwrap room, two multiplug adaptors pluged into each other. 2. Remove noncomplying devices. Two multiplug adaptors pluged into each other in the mail room.
12/27/2006 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. 1. Remove extension cord from portable TV, in the men's shoe display. 2. Remove extension cord in upstairs managers office, replace with a fused multi-plug adaptor.
12/27/2006 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. 1. Electrical outlet shall be protected. Located upstairs in the handbag stock room. 2. Replace electrical box cover, in penthouse equipment room. 3. Repair electrical outlet, in fixture storage room upstairs.
12/27/2006 VIOL - FIRE RESIST.RATED CONST JBURGE Correction Required TFC 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. 1. Repair hole in wall, Lower level, by the fridge in employee break room. 2. Replace missing ceiling tile in lower level men's dept. hub room. 3. Repair holes in wall in electrical room, lower level. 4. Replace missing ceiling tile in electrical room, lower level. 5. Replace missing sprinkler escutcheon in electrical room, lower level. 6. Repair hole in wall in emergency egress corridor, by the men's department. 7. Repair hole in wall, in men's shoes stock room. 8. Replace missing ceiling tile, in men's stock room. 9. Repair hole in wall, in mall door room. 10. Repair hole in wall, in houseware stock room. 11. Repair hole in wall, in camera room by entrance. 12. Replace ceiling tile, in camera room. 13. Repair hole in wall, in luggage stock room. 14. Replace ceiling tile, in luggage stock room. 15. Replace ceiling tile, in bedding stock room. 16. Repair holes in janitor's closet, lower level. 17. Repair holes in electrical panel room, upstairs christmas storage. 18. Repair holes in upstairs visual room. 19. Replace ceiling tile in upstairs visual room. 20. Replace ceiling tile in upstairs lingerie supply room. 21. Replace missing sprinkler escutcheon in jewlry stock room, upstairs. 22. Replace missing sprinkler escutcheon in, upstairs Mac stock room. 23. Replace ceiling tile in upstairs women's shoes, stock room. 24. Repair hole in wall, in upstairs Coach Handbag room. 25. Repair hole in wall, upper level dock.
12/27/2006 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. 1. Replace missing sprinkler head in women's jr. fitting room closet, lower level. 2. Provide documentation of sprinkler system inspection and test date.