Case: T06FR02903
Case Details
Entered Date:
12/19/2006
Applicant:
LCC-1ST/WETMORE LLC
Description:
Inspection
Outstanding Inspections
Case Number: T06FR02903
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/18/2006 | INSP - AST/UST | JLANGEJA | Violation | Dispensers on south islands need vehicle impact protection. |
12/19/2006 | VIOL - MOTOR FUEL DISPENSING | JLANGEJA | Violation | IFC 2206.7.3- Dispensing devices shall be protected against physical damage, shall be mounted on an island of 6" or more or be protected in accordace with Section 312. |
Completed Inspections
Case Status: COMPLETE
Case Number: T06FR02903
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/12/2007 | INSP - REINSPECTION | JLANGEJA | Approved | Bollards have been installed on all dispensers where curb is less than 6" in height. |