Case: T06FR02895
Case Details
Entered Date:
12/15/2006
Applicant:
K-GAM LIMITED PARTNERSHIP
Description:
Full FPI conducted 12/14/06 = RI conducted 1/10
Outstanding Inspections
Case Number: T06FR02895
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
INSP - FULL | None | Not Inspected | ||
01/26/2007 | INSP - REINSPECTION | DGREENLE | Continued | RI 1/25/07 Awaiting stockroom fire hose inspection |
12/15/2006 | VIOL - FIRE SERVICE FEATURES | DGREENLE | Correction Required | 508.5.4 Fire hose in stock room shall not be obstructed. |
12/15/2006 | VIOL - FIRE SERVICE FEATURES | DGREENLE | Correction Required | 508.5.4 Sprinkler system riser and valves shall not be obstructed. |
12/15/2006 | VIOL - FIRE PROTECTION SYSTEMS | DGREENLE | Correction Required | 901.6 Fire hoses in stock room shall be inspected annually. |
12/15/2006 | VIOL - FIRE PROTECTION SYSTEMS | DGREENLE | Correction Required | 903.3.3 Storage on top of security cage shall be removed or sprinkler coverage shall be proveded within cage. |
Completed Inspections
Case Status: COMPLETE
Case Number: T06FR02895
Case Description: INSPECTION
Total Completed Inspections - 6
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/15/2006 | VIOL - HIGH PILED COMBUSTIBLES | DGREENLE | Approved | 2305.4 Aisles in stock room shall be maintained unobstructed a minimum of 44". |
12/15/2006 | VIOL - FIRE RESIST.RATED CONST | DGREENLE | Approved | 703.2 Fire door located at SE corner of sales floor (restroom hall) shall not be propped open. |
12/15/2006 | VIOL - BUILDING SVCS & SYSTEMS | DGREENLE | Approved | 605.6 Electrical outlet near copy machine behind front counter shall have an approved cover. |
12/15/2006 | VIOL - BUILDING SVCS & SYSTEMS | DGREENLE | Approved | 605.6 Electrical outlet on breakroom north wall shall have an approved cover. |
12/15/2006 | VIOL - MEANS OF EGRESS | DGREENLE | Approved | 1008.1.8 Egress door located at SE corner of sales floor (restroom hall) shall be readily openable from teh egress side without key, special knowledge or special effort. |
12/15/2006 | VIOL - MEANS OF EGRESS | DGREENLE | Approved | 1026.5 Emergency lighting at breakroom shall be repaired. |