Case: T06FR02858
Case Details
Entered Date:
12/11/2006
Applicant:
MILLER SCOTT
Description:
Full inspection done 12/11/06. Occupancy- "F-1", Owner- Scott Miller
Outstanding Inspections
Case Number: T06FR02858
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 12
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/11/2006 | VIOL - PRECAUTION AGAINST FIRE | JBURGE | Correction Required | 310.3 “No Smoking” signs. The fire code official is authorized to order the posting of “No Smoking” signs in a conspicuous location in each structure or location in which smoking is prohibited. ***A no smoking sign shall be posted in the garage. |
| 12/11/2006 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. ***Break room, electric wiring in walls and ceiling shall be protected and electric outlet on the ceiling needs an approved cover. |
| 12/11/2006 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | 605.4 Multiplug adapters. Multiplug adaptors, such as cube adaptors, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. ***Replace multi plug adaptor with a fused power strip. |
| 12/11/2006 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. ***Extension cords in compressor room shall be removed. |
| 12/11/2006 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. ***The extension cord in the north side of the garage, used for overhead lighting shall be removed and replaced with a fused power strip. |
| 12/11/2006 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. ***Replace electrical junction box cover in lobby closet. |
| 12/11/2006 | VIOL - FIRE RESIST.RATED CONST | JBURGE | Correction Required | 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. ***Parts room, ceiling tiles shall be replaced. |
| 12/11/2006 | VIOL - FIRE RESIST.RATED CONST | JBURGE | Correction Required | 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. ***Tool room, hole in ceiling shall be repaired. |
| 12/11/2006 | VIOL - FLAMMABLE FINISHES | JBURGE | Correction Required | 1505.7 Dip tank covers. Dip tank covers allowed by Section 1505.6 shall be capable of manual operation and shall be automatic- closing by approved automatic-closing devices designed to operate in the event of fire. ***Replace fuse in solvent tank. |
| 12/12/2006 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | 1008.1.8 Door operations. Egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. ***Remove pad lock from double door in tool room. |
| 12/12/2006 | VIOL - HAZARDOUS MATERIALS,GEN | JBURGE | Correction Required | 2703.3 Release of hazardous materials. Hazardous materials in any quantity shall not be released on the ground, sidewalk, street, highway, or into the atmosphere. ***Dispose of oil on the ground and on concrete slab in an approved manner. |
| 12/13/2006 | VIOL - ADMINISTRATION | JBURGE | Correction Required | 110.4 Abatement. The owner, operator, or occupant of a building or premises deemed unsafe by the fire code official shall abate or cause to be abated or corrected such unsafe conditions either by repair, rehabilitation, demolition or other approved corrective action. ***The wall on the north side of the break room has been deemed hazardous to life and property. This hazard has been refered to (DNR) Department of Neighborhood Resources for further corrective actions. Please feel free to call inspector John Bieg with any questions or concerns at 791-4502. Reinspection is scheduled for 1-03-07 |
Completed Inspections
Case Status: COMPLETE
Case Number: T06FR02858
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/11/2006 | INSP - FULL | JBURGE | Approved | Please correct the following Tucson Fire Code violations: |