MILLER SCOTT

Description:

Full inspection done 12/11/06. Occupancy- "F-1", Owner- Scott Miller

Outstanding Inspections

Case Number: T06FR02858
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 12
End Date Description Inspector Results Comments
12/11/2006 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required 310.3 “No Smoking” signs. The fire code official is authorized to order the posting of “No Smoking” signs in a conspicuous location in each structure or location in which smoking is prohibited. ***A no smoking sign shall be posted in the garage.
12/11/2006 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. ***Break room, electric wiring in walls and ceiling shall be protected and electric outlet on the ceiling needs an approved cover.
12/11/2006 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required 605.4 Multiplug adapters. Multiplug adaptors, such as cube adaptors, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. ***Replace multi plug adaptor with a fused power strip.
12/11/2006 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. ***Extension cords in compressor room shall be removed.
12/11/2006 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. ***The extension cord in the north side of the garage, used for overhead lighting shall be removed and replaced with a fused power strip.
12/11/2006 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. ***Replace electrical junction box cover in lobby closet.
12/11/2006 VIOL - FIRE RESIST.RATED CONST JBURGE Correction Required 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. ***Parts room, ceiling tiles shall be replaced.
12/11/2006 VIOL - FIRE RESIST.RATED CONST JBURGE Correction Required 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. ***Tool room, hole in ceiling shall be repaired.
12/11/2006 VIOL - FLAMMABLE FINISHES JBURGE Correction Required 1505.7 Dip tank covers. Dip tank covers allowed by Section 1505.6 shall be capable of manual operation and shall be automatic- closing by approved automatic-closing devices designed to operate in the event of fire. ***Replace fuse in solvent tank.
12/12/2006 VIOL - MEANS OF EGRESS JBURGE Correction Required 1008.1.8 Door operations. Egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. ***Remove pad lock from double door in tool room.
12/12/2006 VIOL - HAZARDOUS MATERIALS,GEN JBURGE Correction Required 2703.3 Release of hazardous materials. Hazardous materials in any quantity shall not be released on the ground, sidewalk, street, highway, or into the atmosphere. ***Dispose of oil on the ground and on concrete slab in an approved manner.
12/13/2006 VIOL - ADMINISTRATION JBURGE Correction Required 110.4 Abatement. The owner, operator, or occupant of a building or premises deemed unsafe by the fire code official shall abate or cause to be abated or corrected such unsafe conditions either by repair, rehabilitation, demolition or other approved corrective action. ***The wall on the north side of the break room has been deemed hazardous to life and property. This hazard has been refered to (DNR) Department of Neighborhood Resources for further corrective actions. Please feel free to call inspector John Bieg with any questions or concerns at 791-4502. Reinspection is scheduled for 1-03-07

Completed Inspections

Case Status: COMPLETE
Case Number: T06FR02858
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
12/11/2006 INSP - FULL JBURGE Approved Please correct the following Tucson Fire Code violations: