Routine Fire Inspection

Outstanding Inspections

Case Number: T06FR02853
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
12/06/2006 VIOL - FIRE PROTECTION SYSTEMS WCUMMING Correction Required 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. The fire alarm panel in the front office has a ground fault trouble indication and the trouble alarm has been silenced.
12/06/2006 VIOL - MEANS OF EGRESS WCUMMING Correction Required Several emergency exit pathway lights were found inoperative. Repair or replace these lights.
12/06/2006 VIOL - MEANS OF EGRESS WCUMMING Correction Required Several exit signs were found to be inoperative when the test button was activated. Repair or replace the standby storage batteries as needed.
12/06/2006 VIOL - MEANS OF EGRESS WCUMMING Correction Required The left stage exit was obstructed by storage. All required or marked exits and exitways shall be free from all obstructions at all times.