Case: T06FR02853
Case Details
Entered Date:
12/08/2006
Applicant:
TUCSON SCHOOL DISTRICT NO 1
Description:
Routine Fire Inspection
Outstanding Inspections
Case Number: T06FR02853
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 5
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| INSP - FULL | None | Not Inspected | ||
| 12/06/2006 | VIOL - FIRE PROTECTION SYSTEMS | WCUMMING | Correction Required | 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. The fire alarm panel in the front office has a ground fault trouble indication and the trouble alarm has been silenced. |
| 12/06/2006 | VIOL - MEANS OF EGRESS | WCUMMING | Correction Required | Several emergency exit pathway lights were found inoperative. Repair or replace these lights. |
| 12/06/2006 | VIOL - MEANS OF EGRESS | WCUMMING | Correction Required | Several exit signs were found to be inoperative when the test button was activated. Repair or replace the standby storage batteries as needed. |
| 12/06/2006 | VIOL - MEANS OF EGRESS | WCUMMING | Correction Required | The left stage exit was obstructed by storage. All required or marked exits and exitways shall be free from all obstructions at all times. |