Case: T06FR02813
Case Details
Entered Date:
12/01/2006
Applicant:
HOLUALOA CENTRE EAST OFFICE LLC
Description:
FULL FIRE INSPECTION 3 YR INSPECTION CYCLE
Completed Inspections
Case Status: COMPLETE
Case Number: T06FR02813
Case Description: INSPECTION
Total Completed Inspections - 3
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/01/2006 | VIOL - FIRE SERVICE FEATURES | MWAINWRI | Approved | IFC 2003 504.2 Maintenance of exterior doors and openings. Exterior doors and their function shall not be eliminated without prior approval. Exterior doors that have been rendered nonfunctional and that retain a functional door exterior appearance shall have a sign affixed to the exterior side of the door with the words THIS DOOR BLOCKED. EXIT DOOR IN FT OFFICE AT THE NE CORNER, NOT AN EXIT. 1. REMOVE EXIT SIGN AND PLACE "NOT AN EXIT" SIGN INWARD AND "EXIT BLOCKED" SIGN FACING OUTWARD. |
12/01/2006 | VIOL - BUILDING SVCS & SYSTEMS | MWAINWRI | Approved | IFC 2003 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. 1. NEED OUTLET COVER PLATE IN CLOSET OF OFFICE 38. 2. NEED COVER PLATE ON SWITCH IN OFFICE 43. 3. CONDUIT ON EAST WALL OF FT OFFICE NEEDS TO BE SECURED. |
12/01/2006 | INSP - FULL | MWAINWRI | Approved |