Case: T06FR02806
Case Details
Entered Date:
11/30/2006
Applicant:
FIRST AVE/WETMORE OFFICE PLAZA LLC
Description:
FULL FIRE INSPECTION
Completed Inspections
Case Status: COMPLETE
Case Number: T06FR02806
Case Description: INSPECTION
Total Completed Inspections - 3
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/30/2006 | VIOL - BUILDING SVCS & SYSTEMS | SHIGGINB | Approved | IFC 2003 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. 1. ELECRTICAL CONDUTE IN RISER ROOM MUST BE REPAIR, CONDUTE COULD CUT WIRE. |
11/30/2006 | VIOL - FIRE RESIST.RATED CONST | SHIGGINB | Approved | IFC 2003 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. 1. REPAIR CEILING IN SPRINKLER ROOM |
11/30/2006 | INSP - FULL | SHIGGINB | Approved | THIS IS A B2 FULLY SPRINKLERED 3 YR INSPECTION CYCLE |