Case: T06FR02805
Case Details
Entered Date:
11/30/2006
Applicant:
BRYMAR ENTERPRISES LLC
Description:
FULL FIRE INSPETION CHECKLIST USED
Completed Inspections
Case Status: COMPLETE
Case Number: T06FR02805
Case Description: INSPECTION
Total Completed Inspections - 10
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/30/2006 | VIOL - MEANS OF EGRESS | SHIGGINB | Approved | 26.TFC 1008.18 Door operation No double key dead-bolt locks, no special knowledge needed, no slide bolt locks. Only one unlatching device, Except group R’s can have night latch, indicating dead bolt, or security chain on exits only. 1. REMOVE LATCH TYPE LOCK FROM FRONT DOOR, MAY USE A HOTEL NIGHT SWING LOCK |
| 11/30/2006 | VIOL - FIRE RESIST.RATED CONST | SHIGGINB | Approved | 18.TFC 703.1Must be repair w/ fire resistive materials Look behind washers and dryers, hot water heaters, heater closets. 1. REPAIR DRYWALL BEHIND DRYER AND MOVE DRAIN PIPE OUT SIDE THE DRYWALL |
| 11/30/2006 | VIOL - EMERGENCY PLAN/PREPARE | SHIGGINB | Approved | 15. TFC 901.6.2 Records of all system inspections, tests, and maintenance required by the referenced standards shall be maintained on the premises for a minimum of 3 years and made available to the fire code official upon request. 1. SHOW ALL DOCUMENTATION FOR FIRE DRILLS AND SMAKE ALARM TESTING |
| 11/30/2006 | VIOL - FIRE PROTECTION SYSTEMS | SHIGGINB | Approved | 33.TFC 906.1 # 6 Extinguishers required by code official. 1. UNABLE TO FIND FIRE EXTINGUSHER, EITHER SIGN OR MOVE TO BETTER LOCATION. |
| 11/30/2006 | VIOL - FIRE PROTECTION SYSTEMS | SHIGGINB | Approved | 32. TFC 907.2.10 Smoke alarms Check for operation and location. Min. is bedrooms and hallway. 1. ALL SMOKE ALARMS MUST BE BETWEEN 4" AND 12" FROM THE CEILING IF ON A WALL AND 4" FROM CORNER IF ON CEILING. ( BEDROOM 7 AND LIVING ROOM |
| 11/30/2006 | VIOL - BUILDING SVCS & SYSTEMS | SHIGGINB | Approved | 20. TFC 605.5 Extension cords Grounds, used as permanent wiring, run under carpet, attached to walls can be replaced w/ power strip that has overcurrent protection 1.REMOVE EXTENSION CORDS IN BEDROOMS, 2,6 AND 5, LIVING ROOM ( TV) AND BACK PORCH. CAN REPLACE WITH SURGE PROTECTED POWER TAPS. |
| 11/30/2006 | VIOL - BUILDING SVCS & SYSTEMS | SHIGGINB | Approved | 6. TFC 605.1 Abatement of electrical hazards Exposed electrical wires , covers, and panels locked. Undergroud romex can be above 7’ and not in conduit, if protected from UV light and damage. 1. ELECTRICAL WIRES ON N AND S SIDES OF HOME AND SIDE PORCH, MUST SECURED PROPERTY AND PROTECT FROM SUN DAMAGE. 2.POLE ON S. PORCH THAT LEADS TO FOUNTAIN, WIRE MUST BE REPLACE AND PLACED IN CONDUTE |
| 11/30/2006 | VIOL - FIRE SERVICE FEATURES | SHIGGINB | Approved | 4. TFC 506.1 Security devices hindering access A knots box may be required if security devices block access. 1. WINDOW IN 1# BEDROOM IS BLOCKED BY BUSH, CUT BUSH BACK |
| 11/30/2006 | VIOL - PRECAUTION AGAINST FIRE | SHIGGINB | Approved | 2. TFC 304.1.2 Excessive combustibles Must be safe for non self preserving residents. Weeds over 6” high, Look at alleys and around gas meters. Laddering of vegetation to home. 1. WEEDS IN ALLEY MUST BE CUT DOWN |
| 11/30/2006 | INSP - FULL | SHIGGINB | Approved | ASSISTED LIVINF LIC FOR 9 3 YR INSPECTION CYCLE |