Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

11/24/2006

Applicant:

RAME FAMILY LLC

Description:

full inspection

Completed Inspections

Case Status: COMPLETE
Case Number: T06FR02779
Case Description: INSPECTION
Total Completed Inspections - 9
End Date Description Inspector Results Comments
11/24/2006 VIOL - FIRE PROTECTION SYSTEMS DRAMIREZ Approved PRE-CITATION TFC 111.1 "Stop Work Order" The deep vat fryer in operation under the north hood system shall discontinue service untill the system is provided with approved extinguishing system.
11/24/2006 VIOL - FIRE PROTECTION SYSTEMS DRAMIREZ Approved PRE-CITATION TFC 904.2 Hood systems shall be protected with an approved fire-extinguishing system. TFC 904.11 Hood systems shall be tested in accordance with UL/300 standards. The two hood system in operation at this buisness shall meet these requirments.
11/24/2006 VIOL - BUILDING SVCS & SYSTEMS DRAMIREZ Approved TFC 605.4 Cubed adaptors shall be prohibited. Power taps shall be polerized and provided with overcurrent protection.
11/24/2006 VIOL - BUILDING SVCS & SYSTEMS DRAMIREZ Approved TFC 605.6 Approved covers shall be provided for all switch and electrical boxes.
11/24/2006 VIOL - BUILDING SVCS & SYSTEMS DRAMIREZ Approved TFC 605.5 Extension cords shall not be substitutes for permanent wiring.
11/24/2006 VIOL - BUILDING SVCS & SYSTEMS DRAMIREZ Approved TFC 605.1 Electrical conduit shall be secured to wall.
11/24/2006 VIOL - MEANS OF EGRESS DRAMIREZ Approved TFC 1926.5 Emergency backup lighting shall be provided for building.
11/24/2006 VIOL - MEANS OF EGRESS DRAMIREZ Approved TFC 1008.1.8 Sign reading,"THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED", shall be provided and posted adjacent to main enterance door.
11/24/2006 INSP - FULL DRAMIREZ Approved