Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

11/21/2006

Applicant:

GWOZDZ LORRAINE M TR

Description:

Full inspection done 11/20/06. Ace Hardware. Sherry Aekic. 325-7093 "M" occupancy.

Outstanding Inspections

Case Number: T06FR02772
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
11/21/2006 INSP - FULL BCOBB Violation Please correct the following Tucson Fire Code violations: Notes: 1. C of O to be provided upon re-inspection, if available. If not available, manager will be in the process of acquiring it.
11/24/2006 VIOL - MEANS OF EGRESS BCOBB Violation TFC 1027.6 [ammendment] Panic Hardware: Where panic hardware and fire exit hardware is installed, whether required or not, panic or fire exit hardware shall be the only locking device on the door except where otherwise permitted in this code.

Completed Inspections

Case Status: COMPLETE
Case Number: T06FR02772
Case Description: INSPECTION
Total Completed Inspections - 4
End Date Description Inspector Results Comments
11/28/2006 INSP - LIFE SAFETY BCOBB Approved Abated.
11/28/2006 VIOL - COMPRESSED GASES BCOBB Approved Compressed gas bottle secure.
11/28/2006 VIOL - FIRE RESIST.RATED CONST BCOBB Approved Fire door allowed as is [sprinkler present- no factor].
12/27/2006 INSP - REINSPECTION BCOBB Approved All abated. Good job on panic hardware. Approved 12/26/06.