Case: T06FR02755
Case Details
Entered Date:
11/15/2006
Applicant:
VANWOOD INVESTMENT CO
Description:
AST inspection
Outstanding Inspections
Case Number: T06FR02755
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/15/2006 | INSP - AST/UST | JLANGEJA | Correction Required | referred from D. Ramirez for non-permitted AST |
| 11/15/2006 | VIOL - PRECAUTION AGAINST FIRE | JLANGEJA | Violation | IFC 312.2- Vehicle impact protection shall be provided around all storage tanks. Gaurd posts shall comply with the following: 1. constructed of steel not less than 4" in diameter and concrete filled |
| 11/15/2006 | VIOL - FLAMMABLE LIQUIDS | JLANGEJA | Violation | IFC 3403.2.1- A 2-A:20-B:C fire extinguisher shall be installed. |
| 11/15/2006 | VIOL - FLAMMABLE LIQUIDS | JLANGEJA | Violation | IFC 3404.2.7- Storage tanks shall comply with NFPA 30. The tank shall be removed from the pallet and installed as a permanent application. |
Completed Inspections
Case Status: COMPLETE
Case Number: T06FR02755
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/20/2006 | INSP - REINSPECTION | JLANGEJA | Approved | Fire extinguisher and bollards in place. Permit issued. |