Outstanding Inspections

Case Number: T06FR02755
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
11/15/2006 INSP - AST/UST JLANGEJA Correction Required referred from D. Ramirez for non-permitted AST
11/15/2006 VIOL - PRECAUTION AGAINST FIRE JLANGEJA Violation IFC 312.2- Vehicle impact protection shall be provided around all storage tanks. Gaurd posts shall comply with the following: 1. constructed of steel not less than 4" in diameter and concrete filled
11/15/2006 VIOL - FLAMMABLE LIQUIDS JLANGEJA Violation IFC 3403.2.1- A 2-A:20-B:C fire extinguisher shall be installed.
11/15/2006 VIOL - FLAMMABLE LIQUIDS JLANGEJA Violation IFC 3404.2.7- Storage tanks shall comply with NFPA 30. The tank shall be removed from the pallet and installed as a permanent application.

Completed Inspections

Case Status: COMPLETE
Case Number: T06FR02755
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
12/20/2006 INSP - REINSPECTION JLANGEJA Approved Fire extinguisher and bollards in place. Permit issued.