Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

10/10/2006

Applicant:

GRANT ROAD INDUSTRIAL LLC

Description:

Full inspection

Completed Inspections

Case Status: COMPLETE
Case Number: T06FR02657
Case Description: INSPECTION
Total Completed Inspections - 4
End Date Description Inspector Results Comments
10/10/2006 VIOL - BUILDING SVCS & SYSTEMS DRAMIREZ Approved TFC 605.6 Covers shall be provided for open junction boxes
10/10/2006 VIOL - BUILDING SVCS & SYSTEMS DRAMIREZ Approved TFC 605.3 A working space and clearance area of 36 inches shall be provided in front of electrical panel.
10/10/2006 VIOL - FIRE PROTECTION SYSTEMS DRAMIREZ Approved TFC 901.8 Newly installed insullation on ceiling in warehouse area is obstructing the fire suppression system. Shall remove insullation or extend sprinkler heads below insullation, according to code.
10/10/2006 INSP - FULL DRAMIREZ Approved The property owner, Burris, Hennessy & Co. 882-4343, respectfully requests to be contacted prior to inspection or for any business pertaining to any suite in the building at 1802 W. Grant Rd.