Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

09/26/2006

Applicant:

GRANT ROAD INDUSTRIAL LLC

Description:

FULL INSPECTION

Completed Inspections

Case Status: COMPLETE
Case Number: T06FR02607
Case Description: INSPECTION
Total Completed Inspections - 7
End Date Description Inspector Results Comments
07/31/2006 VIOL - FIRE RESIST.RATED CONST DRAMIREZ Approved TFC 703.1 Damaged ceiling tiles shall be repaired or replaced to prevent the passage of smoke or fire.
07/31/2006 VIOL - MEANS OF EGRESS DRAMIREZ Approved TFC1008.1.8 You shall provide a thumb-turn lock for the door leading to the workshop area.
07/31/2006 VIOL - MEANS OF EGRESS DRAMIREZ Approved TFC 1027.2 Required exits shall be maintained free of obstructions and impedements at all times.
07/31/2006 INSP - LIFE SAFETY DRAMIREZ Approved TFC 605.3 A working space and clearance area of at 36 inches shall be provided in front of an electrical panel.
07/31/2006 INSP - LIFE SAFETY DRAMIREZ Approved TFC 605.4 Misuse of multiplug adaptors.
07/31/2006 INSP - LIFE SAFETY DRAMIREZ Approved TFC 605.5 Extention caords shall not be substitute for prmanent wiring.
07/31/2006 INSP - FULL DRAMIREZ Approved This inspection was initiated on 7-31-06, completed on 8-14-06