Case: T06FR02583
Case Details
Entered Date:
09/15/2006
Applicant:
TUCSON HOUSE APARTMENTS LP
Description:
inspection
Outstanding Inspections
Case Number: T06FR02583
Case Status: REFERRED
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/15/2006 | INSP - FULL | EGRIFFIN | Violation | 1).2- Exit lights are out of service and shall be repaired IFC 1026.3 2). Fire sprinkler shall be tested and results shall be sent to TFD. IFC 901.6 3). Fire alarm test shall be provided and smoke detectors shall be addressed on test report. IFC 901.6 |
10/12/2006 | INSP - REINSPECTION | EGRIFFIN | Continued | referred to city building inspector |