Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

REFERRED

Type:

INSPECTION
Address:

Entered Date:

09/15/2006

Applicant:

TUCSON HOUSE APARTMENTS LP

Description:

inspection

Outstanding Inspections

Case Number: T06FR02583
Case Status: REFERRED
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
09/15/2006 INSP - FULL EGRIFFIN Violation 1).2- Exit lights are out of service and shall be repaired IFC 1026.3 2). Fire sprinkler shall be tested and results shall be sent to TFD. IFC 901.6 3). Fire alarm test shall be provided and smoke detectors shall be addressed on test report. IFC 901.6
10/12/2006 INSP - REINSPECTION EGRIFFIN Continued referred to city building inspector