Case: T06FR02576
Case Details
Entered Date:
09/14/2006
Applicant:
GRUNSTEIN ROBERT
Description:
Full Inspection
Outstanding Inspections
Case Number: T06FR02576
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 14
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/14/2006 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.6 Electrical junction box at basement stairs shall have a cover. |
| 09/14/2006 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1008.1.8 Exit door at the patio on the south side shall be openable from the inside without a key. |
| 09/14/2006 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1008.1.8 Exit door at west end of basement shall be openable from the inside without a key. |
| 09/14/2006 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1008.1.8 Exit door located at northeast room shall be openable without a key. |
| 09/14/2006 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1008.1.8 Exit door located at northeast room shall be openable without a key. West end of wall. |
| 09/14/2006 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1008.1.8 Exit door located at southwest corner of northside room shall be openable without a key. |
| 09/14/2006 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1013.4.1 Aisles throughout store shall be maintained 3 feet in public areas and 28 inches in nonpublic areas. |
| 09/14/2006 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1026.3 Exit sign located at the basement at the bottom of stairs shall be repaired. |
| 09/14/2006 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1026.3 Exit sign located at the basement at the west end shall be repaired. |
| 09/14/2006 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1026.5 Emergency lights at basement shall be repaired. |
| 09/14/2006 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027 Deadbolt lock on panic hardware equipped door. Located at northeast exit south wall. |
| 09/14/2006 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027 Deadbolt lock on panic hardware equipped door. Located at southeast exit. |
| 09/14/2006 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027.2 Exit at northwest storage room, south wall, west end, shall not be obstructed. |
| 09/14/2006 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027.2 Exit at southwest corner of north side room shall not be obstructed. |
Completed Inspections
Case Status: COMPLETE
Case Number: T06FR02576
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/30/2006 | INSP - FULL | TKNAPP | Approved |