Case: T06FR02533
Case Details
Entered Date:
09/06/2006
Applicant:
LA FRONTERA CENTER INC
Description:
inspection
Outstanding Inspections
Case Number: T06FR02533
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| COMPLIANCE | None | Not Inspected |
Completed Inspections
Case Status: COMPLETE
Case Number: T06FR02533
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/06/2006 | INSP - FULL | EGRIFFIN | Approved | 1). According to your certificate of occupancy dated 1994, smoke detectors are required under UFC 1991 Appendix 1-A in all sleeping quarters. You have an extension until 9-29-06 to install these smoke detectors. IFC 901.6 and 91 UFC APP 1-a 2). Remove combustible material from electrical room. IFC 315.2.3 3). Exit light is out in kitchen and shall be repaired. IFC 1026.3 4). Fire alarms shall be tested. Heat detectors shall be addressed on alarm test. IFC 901.6 5). Fire sprinklers shall be tested and report submitted to TFD, with all required repairs completed. IFC 901.6 6). Remove boxes from stairs. IFC 1027.3 |