Case: T06FR02508
Case Details
Entered Date:
08/29/2006
Applicant:
DOLNY CARMEN A
Description:
Inspection
Outstanding Inspections
Case Number: T06FR02508
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/29/2006 | INSP - AST/UST | JLANGEJA | Correction Required | This was a complaint from Capt. Jones of a fuel odor coming from the AM/PM. He said someone was working on the dispensers and that I should check it out. |
| 08/29/2006 | VIOL - MOTOR FUEL DISPENSING | JLANGEJA | Violation | IFC 2205.2.1- Maintenance to Class I liquid dispensing devices shall comply with the following: 1. Only persons knowledgeable shall perform work. 2. Electrical power shall be shut off at the main electrical panel. 3. The emergency shut off valve at the dispenser shall be closed. 4. Vehicle traffic and unauthorized persons shall be prevented from coming within 12 feet of the dispensing device. Any further violations will result in a citation which will require an appearance in court and a probable fine. |
Completed Inspections
Case Status: COMPLETE
Case Number: T06FR02508
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/11/2007 | INSP - REINSPECTION | JLANGEJA | Approved | Follow up at other sites shows Vista following proper requirements for dispenser repairs. |