Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

08/22/2006

Applicant:

REAY'S RANCH INVESTORS LLC

Description:

Inspection

Outstanding Inspections

Case Number: T06FR02477
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
08/21/2006 INSP - FULL JLANGEJA Correction Required This was referred by EN09-C for alarm #46689. They requested an inspection of the premises, particularly the nozzle and dispenser that caused the fuel spill.
08/21/2006 VIOL - MOTOR FUEL DISPENSING JLANGEJA Violation IFC 2205.2- Equipment maintenance and inspection. Motor fuel-dispensing facility equipment shall be maintained in proper working condition at all times. *Nozzle to dispenser #6 was replaced. Repair order will be faxed to Fire Prevention at # below.
08/21/2006 VIOL - MOTOR FUEL DISPENSING JLANGEJA Violation IFC 2205.2.2- Emergency shut off valves. Automatic-closing emergency shut off valves required by Section 2206.7.4 shall be checked not less than once per year by manually tripping the hold-open linkage.

Completed Inspections

Case Status: COMPLETE
Case Number: T06FR02477
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
08/28/2006 COMPLIANCE JLANGEJA Approved All violations have been corrected.