Case: T06FR02477
Case Details
Entered Date:
08/22/2006
Applicant:
REAY'S RANCH INVESTORS LLC
Description:
Inspection
Outstanding Inspections
Case Number: T06FR02477
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/21/2006 | INSP - FULL | JLANGEJA | Correction Required | This was referred by EN09-C for alarm #46689. They requested an inspection of the premises, particularly the nozzle and dispenser that caused the fuel spill. |
| 08/21/2006 | VIOL - MOTOR FUEL DISPENSING | JLANGEJA | Violation | IFC 2205.2- Equipment maintenance and inspection. Motor fuel-dispensing facility equipment shall be maintained in proper working condition at all times. *Nozzle to dispenser #6 was replaced. Repair order will be faxed to Fire Prevention at # below. |
| 08/21/2006 | VIOL - MOTOR FUEL DISPENSING | JLANGEJA | Violation | IFC 2205.2.2- Emergency shut off valves. Automatic-closing emergency shut off valves required by Section 2206.7.4 shall be checked not less than once per year by manually tripping the hold-open linkage. |
Completed Inspections
Case Status: COMPLETE
Case Number: T06FR02477
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/28/2006 | COMPLIANCE | JLANGEJA | Approved | All violations have been corrected. |