Case: T06FR02473
Case Details
Entered Date:
08/21/2006
Applicant:
GEE D & J TR
Description:
Full Inspection
Outstanding Inspections
Case Number: T06FR02473
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 9
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
INSP - FULL | None | Not Inspected | ||
08/21/2006 | VIOL - EMERGENCY PLAN/PREPARE | JDAVIS | Correction Required | IFC 2003 Section 407.2/ 2703.2 Provide MSDS for all Chemicals: -Must be accessible -Train employees |
08/21/2006 | VIOL - BUILDING SVCS & SYSTEMS | JDAVIS | Correction Required | IFC 605.5 Do not use extension cords as a substitute for permanent wiring: -Steves' office -service counter -Service office -Shed in rear of business -service dept: North wall to lights |
08/21/2006 | VIOL - MEANS OF EGRESS | JDAVIS | Correction Required | IFC 2003 1008.1.8.4 Slide bolts are prohibited on exit doors: -East and West exit doors |
08/21/2006 | VIOL - HAZARDOUS MATERIALS,GEN | JDAVIS | Correction Required | IFC 2703.5 Provide 704M placard on the shed on both the East and West sides. 1-3-0-blank |
08/21/2006 | VIOL - HAZARDOUS MATERIALS,GEN | JDAVIS | Correction Required | IFC 2705.5/ 3403.5 Label 55 gallon drums "USED OIL". |
08/21/2006 | VIOL - COMPRESSED GASES | JDAVIS | Correction Required | IFC 3003.3 Compressed gas cylinders shall be secured: -Front office Service dept. Parts |
08/21/2006 | VIOL - FLAMMABLE LIQUIDS | JDAVIS | Correction Required | IFC 2003 Section 3405.3.6.2 Repair the mecanism arm on the parts cleaner in the shed. |
08/21/2006 | VIOL - FLAMMABLE LIQUIDS | JDAVIS | Correction Required | IFC 3405.3.7.5.4/ 3404.3.8.3 Rooms storing Flammable liquids shall have proper ventilation: |