Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

08/16/2006

Applicant:

QUIJADA MARTHA YOLANDA

Description:

FIRE INSPECTION CHECK L IST USED

Completed Inspections

Case Status: COMPLETE
Case Number: T06FR02448
Case Description: INSPECTION
Total Completed Inspections - 7
End Date Description Inspector Results Comments
12/28/2006 VIOL - FIRE PROTECTION SYSTEMS SHIGGINB Approved 32. TFC 907.2.10 Smoke alarms Check for operation and location. Min. is bedrooms and hallway 1. REPAIR SMOKE ALARM IN BEDROOM # 6, AND LAUNTRY ROOM, AND OFFICE. 2. SMOKE ALARM IN DINING TO LOW, MUST BETWEEN 4 TO 12" FROM CEILING OR ON CEILING.
12/28/2006 VIOL - BUILDING SVCS & SYSTEMS SHIGGINB Approved 20. TFC 605.5 Extension cords Grounds, used as permanent wiring, run under carpet, attached to walls can be replaced w/ power strip that has overcurrent protection. 1. REMOVE EXTEN. CORD IN NE BEDROOM AND IN BEDROOM # 7.
12/28/2006 VIOL - BUILDING SVCS & SYSTEMS SHIGGINB Approved 21.TFC 605.4 Multi-plugs and power-taps UL listed,No end to end, home made. 1. REMOVE MULTI-PLUG ADAPTERS IN LIVING ROOM AND BEDROOM # 8. MAY REPLACE W/ A PROTECTED POWER TAP.
12/28/2006 VIOL - BUILDING SVCS & SYSTEMS SHIGGINB Approved 6. TFC 605.1 Abatement of electrical hazards Exposed electrical wires , covers, and panels locked. Undergroud romex can be above 7’ and not in conduit, if protected from UV light and damage. 1. SECURE ELEC. WIRE UNDER EVES ON FRONT PORCH 2. EXPOSED ELEC. WIRE N. SIDE OF BUILDING. ABOVE ELEC. PANEL NEEDS TO PLACE IN CONDUTE.
12/28/2006 VIOL - FIRE SERVICE FEATURES SHIGGINB Approved 3. TFC 503.1.1 Emergency Unit access Apparatus must be able to get within 150’, around the building. Fire lanes 20’w x 15’h. 1.MUST HAVE FIRE DEPART. ACCESS FOR FRONT GATE. ( MAY NEED A KNOT BOX )
12/28/2006 VIOL - PRECAUTION AGAINST FIRE SHIGGINB Approved 2. TFC 304.1.2 Excessive combustibles Must be safe for non self preserving residents. Weeds over 6” high, Look at alleys and around gas meters. Laddering of vegetation to home. 1. TRIM BUSHES AND TREES, KEEP 3' AWAY FROM BUILDING.
12/28/2006 INSP - FULL SHIGGINB Approved FULL FIRE INSPECTION IFC 2003 CODE USED ASL HOME LIC FOR 10