Description:

FIRE INSPECTION CHECK LIST USED

Completed Inspections

Case Status: COMPLETE
Case Number: T06FR02444
Case Description: INSPECTION
Total Completed Inspections - 12
End Date Description Inspector Results Comments
12/12/2006 VIOL - BUILDING SVCS & SYSTEMS SHIGGINB Approved IFC 2003 6. TFC 605.1 Abatement of electrical hazards Exposed electrical wires , covers, and panels locked. Undergroud romex can be above 7’ and not in conduit, if protected from UV light and damage. 1. ELECTRICAL WIRE LEADING TO IRRIGATION BOX MUST BE REPLACES AND PLACED IN CONDUIT. 2.ELECTRICAL WIRE FROM PANEL IS EXPOSED AND NEEDS TO BE PLACED TO CONDUIT.
12/12/2006 INSP - FULL SHIGGINB Approved ASL HOME LIC 10 COF O FROM 3/19/97
02/20/2007 VIOL - COMPRESSED GASES MWAINWRI Approved
02/20/2007 VIOL - COMPRESSED GASES MWAINWRI Approved 2003 IFC TFC 3004.1 O2 storage and UseCan be on a 45 degree, Must be secured w/ straps or rack No smoking signs must be posted on front door SECURE OXYGEN BOTTLES IN CLOSET
02/20/2007 VIOL - FIRE PROTECTION SYSTEMS MWAINWRI Approved
02/20/2007 VIOL - FIRE PROTECTION SYSTEMS MWAINWRI Approved 2003 IFC 907.2.10 Smoke alarms Check for operation and location. Min. is bedrooms and hallway REPAIR SMOKE ALARM IN THE EAST BEDROOM OFF THE WEST HALLWAY.
02/20/2007 VIOL - MEANS OF EGRESS MWAINWRI Approved
02/20/2007 VIOL - MEANS OF EGRESS MWAINWRI Approved 2003 IFC TFC 605.5 Extension cords Grounds, used as permanent wiring, run under carpet, attached to walls can be replaced w/power strip that has overcurrent protection REMOVE EXTENSION CORDS FROM THE EAST BEDROOM OF THE WEST HALLWAY.
02/20/2007 VIOL - MEANS OF EGRESS MWAINWRI Approved 2003 IFC 1027.2 Maintenance of egress components Paths, doors, and ramps. Signs required in BHS The path is to a public way or a safe place 1) REMOVE TOP DOOR KNOB AND REPLACE WITH A THUMB TURN DEAD BOLT OR NIGHT LATCH. 2) WEST BEDROOM, REMOVE DOUBLE KEYED DEADBOLT ON SECURTY GATE. REPLACE WITH THUMB TURN DEADBOLT.
02/20/2007 VIOL - FIRE RESIST.RATED CONST MWAINWRI Approved
02/20/2007 VIOL - FIRE RESIST.RATED CONST MWAINWRI Approved 2003 IFC TFC 603.1 & 316.2 Fuel fired appliances and house cleaning. Furnaces, dryer and hot water heaters are all heat sources and must be maintained and cleaned. DO NOT STORE COMBUSTABLES NEAR WATER HEATER. REMOVE ITEMS.
02/20/2007 VIOL - FIRE RESIST.RATED CONST MWAINWRI Approved 2003 IFC 703.1Must be repair w/ fire resistive materials Look behind washers and dryers, hot water heaters, heater closets REPAIR FIRE RESISTIVE MATERIALS IN WATER HEATER CLOSET. INSTALL DRYWALL ON WALLS AND INSTALL A COMBUSTABLE VENT ON BACK OF HOTWATER WALL 6FT FROM FLOOR.