Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

07/28/2006

Applicant:

WETMORE PLAZA LLC

Description:

Full Inspection

Completed Inspections

Case Status: COMPLETE
Case Number: T06FR02335
Case Description: INSPECTION
Total Completed Inspections - 7
End Date Description Inspector Results Comments
07/28/2006 VIOL - PRECAUTION AGAINST FIRE DRAMIREZ Approved TFC 315.2.1 Stored materials are obstructing the sprinkler heads located in the front supply room. A minimum of 18 inches of clearance shall be provided for all sprinkler heads.
07/28/2006 VIOL - PRECAUTION AGAINST FIRE DRAMIREZ Approved TFC 315.2.3 Gasoline cans being stored in" PUMP ROOM "shall be removed.
07/28/2006 VIOL - BUILDING SVCS & SYSTEMS DRAMIREZ Approved TFC 605.3.1 You shall identify the electrical room with a sign reading:" ELECTRICAL ROOM "
07/28/2006 VIOL - BUILDING SVCS & SYSTEMS DRAMIREZ Approved TFC 605.6 Cover plates shall be provided for open breakers in electrical panel box.
07/28/2006 VIOL - MEANS OF EGRESS DRAMIREZ Approved TFC 1011.1 Exit signs shall be provided for the E. side door located in the " BASICS " classroom.
07/28/2006 VIOL - MEANS OF EGRESS DRAMIREZ Approved TFC 1008.1.8 The double exterior doors located in the STAFF room shall be provided with a thumb-turn bolt.
07/28/2006 INSP - FULL DRAMIREZ Approved TFC 703.1 Openings on ceiling tile and walls shall be protected from passage of smoke and fire. Areas identified: 1.) front supply room, ceiling tile. 2.) front supply room, hole in wall behind door. 3.) " BASICS" classroom, missing ceiling tile. 4.) " POOL PUMP " room, holes in wall .