Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

07/28/2006

Applicant:

DEUTSCH FAMILY TR

Description:

Full Inspection

Completed Inspections

Case Status: COMPLETE
Case Number: T06FR02333
Case Description: INSPECTION
Total Completed Inspections - 14
End Date Description Inspector Results Comments
07/28/2006 VIOL - ADMINISTRATION DRAMIREZ Approved TFC105.1.1 Opreational permit is required to store motor oil in quantities that exeed 60 gallons.
07/28/2006 VIOL - MOTOR FUEL DISPENSING DRAMIREZ Approved TFC 2206.7.5.1 The diesel fuel dispenser hose on the # 8 pump shall be provided with a breakaway device.
07/28/2006 VIOL - FIRE SERVICE FEATURES DRAMIREZ Approved TFC 505.1 Address numbers shall be provided for the building and shall be visable from the street fronting the property.
07/28/2006 VIOL - COMPRESSED GASES DRAMIREZ Approved TFC 3030.3 Compressed gas cylinders shall be secured against accidental dislodgement.
07/28/2006 VIOL - FIRE PROTECTION SYSTEMS DRAMIREZ Approved TFC 906.5 Portable extinguishers shall be located in conspicuous locations and installed on hangers or brackets.
07/28/2006 VIOL - FIRE PROTECTION SYSTEMS DRAMIREZ Approved TFC 906.2 / TFC 2205.5 Portable fire extinguisher shall be provided in the shop area with a minimum of a 10-20 B:C rating.
07/28/2006 VIOL - FIRE PROTECTION SYSTEMS DRAMIREZ Approved TFC 901.6 The self-closing mechanism for the lid on the " parts washer " has been alterd to keep the lid in the open position at all times rendering it unclosable in the event of a fire.
07/28/2006 VIOL - PRECAUTION AGAINST FIRE DRAMIREZ Approved TFC 310.2 " NO SMOKING " signs shall be provided where flammable or combustible materials are stored or handled.
07/28/2006 VIOL - PRECAUTION AGAINST FIRE DRAMIREZ Approved TFC 304.3.1 Oily rags shall be stored in approved noncombustable containers with self-closing lids.
07/28/2006 VIOL - FIRE RESIST.RATED CONST DRAMIREZ Approved TFC 703.1 Openings on ceilings or walls shall be protected from passage of smoke or fire.
07/28/2006 VIOL - BUILDING SVCS & SYSTEMS DRAMIREZ Approved TFC 605.1 Exposed wiring on power cord to tire changer.
07/28/2006 VIOL - BUILDING SVCS & SYSTEMS DRAMIREZ Approved TFC 605.6 Cover plate shall be provided for open electrical box,shop area SW corner close to ceiling.
07/28/2006 VIOL - BUILDING SVCS & SYSTEMS DRAMIREZ Approved TFC 605.4 Multiplug adapters, unapproved, in shop area N. wall next to cabinet
07/28/2006 INSP - FULL DRAMIREZ Approved