Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T06FR02316
Case Details
Entered Date:
07/26/2006
Applicant:
UNITED WAY CAPITAL CORP
Description:
inspection
Outstanding Inspections
Case Number: T06FR02316
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/26/2006 | INSP - FULL | EGRIFFIN | Violation | 1). Fire alarm report shall be submitted to TFD, and all corrections shall be made. IFC 901.6 2). NFPA 72 (The National Fire Code) 11.5.8.1 states: Smoke detectors shall be installed in all day care sleeping quarters. Currently there are none. Smoke detectors shall be installed in all sleeping quarters as discussed. 3). Door closure in office shall be repaired, and office door shall remian closed as per IFC 703.2.2 703.2.2 Hold-open devices and closers. Hold-open devices and automatic door closers, where provided, shall be maintained. During the period that such device is out of service for repairs, the door it operates shall remain in the closed position. 4). Remove all combustible material from mechanical room. IFC 315.2.3 |
Completed Inspections
Case Status: COMPLETE
Case Number: T06FR02316
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/22/2006 | COMPLIANCE | EGRIFFIN | Approved | approved |