Case: T06FR02290
Case Details
Entered Date:
07/25/2006
Applicant:
YACOUB BUSINESS ENTERPRISES INC
Description:
full inspection
Completed Inspections
Case Status: COMPLETE
Case Number: T06FR02290
Case Description: INSPECTION
Total Completed Inspections - 15
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/25/2006 | VIOL - BUILDING SVCS & SYSTEMS | DRAMIREZ | Approved | TFC 605.1 Electrical conduit extending from ceiling to floor is dislodged, movable by shoppers ,creating electrical hazard. |
07/25/2006 | VIOL - BUILDING SVCS & SYSTEMS | DRAMIREZ | Approved | TFC 605.4 Use of multiple adapters other then polerized grounded type with over current protection. |
07/25/2006 | VIOL - BUILDING SVCS & SYSTEMS | DRAMIREZ | Approved | TFC 605.6 Open electrical boxes in the following locations: 1.) in the deli area close to floor by counter. 2.) electrical panel in stockroom. |
07/25/2006 | VIOL - BUILDING SVCS & SYSTEMS | DRAMIREZ | Approved | TFC 605.5 Extension cord misuse in the following locations: 1.) to the ice cream box located at front window. 2.) behind ice box located at front window. 3.) running through ceiling over hot dog rotisserie. |
07/25/2006 | VIOL - FIRE SERVICE FEATURES | DRAMIREZ | Approved | TFC 505.1 Address numbers shall be visable from the street fronting the property. |
07/25/2006 | INSP - FULL | DRAMIREZ | Approved | |
07/26/2006 | VIOL - MOTOR FUEL DISPENSING | DRAMIREZ | Approved | TFC 2206.7.5.1 The breakaway devices for dispenser hoses shall be installed and maintained . The breakaway device for the diesel pumps shall be located between the nozzle and the point of attachment of the hose retfactor cable to the hose. |
07/26/2006 | VIOL - MOTOR FUEL DISPENSING | DRAMIREZ | Approved | TFC 2203.3 Emergency fuel shut-off shall be clearly identified and readily accessable. |
07/26/2006 | VIOL - COMPRESSED GASES | DRAMIREZ | Approved | TFC 3003.3 Unsecured CO2 cylinder in stock room. |
07/26/2006 | VIOL - FIRE RESIST.RATED CONST | DRAMIREZ | Approved | TFC 703.1 Opening in ceiling and walls in following areas. 1.) on ceiling over restroom area. 2.) in the deli area next to counter , by floor. |
07/26/2006 | VIOL - FIRE PROTECTION SYSTEMS | DRAMIREZ | Approved | TFC 901.6 Portable extinguishers provided, required or not shall be maintained and serviced or removed. |
07/26/2006 | VIOL - FIRE PROTECTION SYSTEMS | DRAMIREZ | Approved | TFC 906.5 Portable extinguishers shall be located in conspicuous locations and installed in hangers or brakets. |
07/26/2006 | VIOL - FIRE PROTECTION SYSTEMS | DRAMIREZ | Approved | TFC 906.2 Portable extinguishers shall be maintained and serviced annually |
07/26/2006 | VIOL - MEANS OF EGRESS | DRAMIREZ | Approved | TFC 1011.2 Exit signs shall be illuminated. |
07/26/2006 | VIOL - MEANS OF EGRESS | DRAMIREZ | Approved | TFC 1008.1.8.4 Bolt locks / Both side doors are provided with bolt locks. Bolt lock on side door to the north was removed. Bolt lock to side door to the south was allowed to remain for added security. This door is also damaged and out of service. |