Case Status: COMPLETE
Case Number: T06FR02288
Case Description: INSPECTION
Total Completed Inspections - 4
End Date Description Inspector Results Comments
07/25/2006 VIOL - FIRE RESIST.RATED CONST DRAMIREZ Approved TFC 703.1 Ceiling tile needs replacing in the following: 1.) storage room. 2.) both supervisors offices.
07/25/2006 VIOL - FIRE SERVICE FEATURES DRAMIREZ Approved TFC 605.6 Open junction boxes in the following locations: 1.) on the wall next to floor in the storage room. 2.) electrical panel in storage room.
07/25/2006 VIOL - FIRE SERVICE FEATURES DRAMIREZ Approved TFC 605.5 Misuse of extention cords in the main lobby.
07/25/2006 INSP - FULL DRAMIREZ Approved