Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

07/19/2006

Applicant:

THOMPSON PAUL K & HOLLY E JT/RS

Description:

inspection

Outstanding Inspections

Case Number: T06FR02256
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
07/19/2006 INSP - FULL EGRIFFIN Violation 1). Exit light shall be repaired on front door area and back door area. IFC 1011.2 2). Door hardware is to high all shall be lowered as per; 1008.1.8.2 Hardware height. Door handles, pulls, latches, locks and other operating devices shall be installed 34 inches (864 mm) minimum and 48 inches (1219 mm) maximum above the finished floor. Locks used only for security purposes and not used for normal operation are permitted at any height.

Completed Inspections

Case Status: COMPLETE
Case Number: T06FR02256
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
07/31/2006 COMPLIANCE EGRIFFIN Approved approved