Case: T06FR02213
Case Details
Entered Date:
07/13/2006
Applicant:
CARRANZA JOAQUIN C JR & VERONICA CP/RS
Description:
FIRE INSPECTION CHECLIST USED
Completed Inspections
Case Status: COMPLETE
Case Number: T06FR02213
Case Description: INSPECTION
Total Completed Inspections - 5
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/13/2006 | VIOL - BUILDING SVCS & SYSTEMS | SHIGGINB | Approved | 20. TFC 605.5 Extension cords Grounds, used as permanent wiring, run under carpet, attached to walls can be replaced w/ power strip that has overcurrent protection 1. REMOVE EXTENSION CORDS |
| 07/13/2006 | VIOL - MEANS OF EGRESS | SHIGGINB | Approved | 31. TFC 1026.5 Emergecy ligting Required in Group R if over 10, and must have 2 exits. Exception: If each sleeping room has a direct exit to the outside. 1. REPAIR EMERGENCY LIGHTING IN HALLWAY |
| 07/13/2006 | VIOL - MEANS OF EGRESS | SHIGGINB | Approved | 26.TFC 1008.18 Door operation No double key dead-bolt locks, no special knowledge needed, no slide bolt locks. Only one unlatching device, Except group R’s can have night latch, indicating dead bolt, or security chain on exits only 1. REMOVE DOUBLE KEY DEAD BOLT FROM REAR DOOR AND FRONT SCREN DOOR |
| 07/13/2006 | VIOL - FIRE RESIST.RATED CONST | SHIGGINB | Approved | 18.TFC 703.1Must be repair w/ fire resistive materials Look behind washers and dryers, hot water heaters, heater closets 1.REPAIR CEILING IN E. WATER HEATER CLOSET |
| 07/13/2006 | INSP - FULL | SHIGGINB | Approved | ASL HOME LIC FOR 5 INVALIDS |