Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Case Details

Status:

FIELD

Type:

INSPECTION
Address:

Entered Date:

07/10/2006

Applicant:

METAL MAN INC

Description:

inspection

Outstanding Inspections

Case Number: T06FR02184
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
07/10/2006 VIOL - FIRE PROTECTION SYSTEMS JVALENZU Violation 901.6 - fire extinguishers shall be serviced annually - inside paint booth, all extinguishers expire July 2006
07/10/2006 VIOL - FLAMMABLE FINISHES JVALENZU Violation 1504.6 - Spray booths shall be protected by an approved automatic extinguishing system - none present in paint booth or building.
07/10/2006 VIOL - HAZARDOUS MATERIALS,GEN JVALENZU Violation 2703.1.1(1) - The maximum allowable quantity of flammable gas in storage or use is 1,000 cubic feet @ NTP. - currently 2 large acetylene bottles manifolded for use.