Case: T06FR02184
Case Details
Entered Date:
07/10/2006
Applicant:
METAL MAN INC
Description:
inspection
Outstanding Inspections
Case Number: T06FR02184
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 4
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| INSP - FULL | None | Not Inspected | ||
| 07/10/2006 | VIOL - FIRE PROTECTION SYSTEMS | JVALENZU | Violation | 901.6 - fire extinguishers shall be serviced annually - inside paint booth, all extinguishers expire July 2006 |
| 07/10/2006 | VIOL - FLAMMABLE FINISHES | JVALENZU | Violation | 1504.6 - Spray booths shall be protected by an approved automatic extinguishing system - none present in paint booth or building. |
| 07/10/2006 | VIOL - HAZARDOUS MATERIALS,GEN | JVALENZU | Violation | 2703.1.1(1) - The maximum allowable quantity of flammable gas in storage or use is 1,000 cubic feet @ NTP. - currently 2 large acetylene bottles manifolded for use. |