Case: T06FR02160
Case Details
Entered Date:
07/06/2006
Applicant:
AMADO CARLOS A & SYLVIA 50% & AMADO
Description:
inspection
Outstanding Inspections
Case Number: T06FR02160
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 5
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| INSP - FULL | None | Not Inspected | ||
| 04/27/2006 | VIOL - BUILDING SVCS & SYSTEMS | JVALENZU | Violation | 605.3 - a clear working space of not less than 30''w x 36''d x 78''h shall be provided in front of electrical service equipment - front office and printing area |
| 04/27/2006 | VIOL - BUILDING SVCS & SYSTEMS | JVALENZU | Violation | 605.4 - multiplug adapters shall be prohibited - lights in printing area |
| 04/27/2006 | VIOL - BUILDING SVCS & SYSTEMS | JVALENZU | Violation | 605.5 - extension cords shall not be used as a substitute for permanent wiring - printing area |
| 04/27/2006 | VIOL - FIRE PROTECTION SYSTEMS | JVALENZU | Violation | 906.7 - extinguishers shall be mounted on hangars or brackets - front office and printing area |