Case: T06FR02144
Case Details
Entered Date:
07/03/2006
Applicant:
MAQSOOD AND SONS LLC
Description:
Full Inspection
Outstanding Inspections
Case Number: T06FR02144
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
INSP - FULL | None | Not Inspected |
Completed Inspections
Case Status: COMPLETE
Case Number: T06FR02144
Case Description: INSPECTION
Total Completed Inspections - 6
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/03/2006 | VIOL - FIRE RESIST.RATED CONST | DRAMIREZ | Approved | TFC 703.1Ceiling tiles in office shall be repaired restored or replaced. |
07/03/2006 | VIOL - BUILDING SVCS & SYSTEMS | DRAMIREZ | Approved | TFC 605.6 Open junction boxes shall not be provided with approved covers. Provide cover for open j. box in area ajacent to office. |
07/03/2006 | VIOL - BUILDING SVCS & SYSTEMS | DRAMIREZ | Approved | TFC605.5 Extension cords shall not be a substitute for permenant wiring. Misuse of ext. cords in the following locations: 1.) ajacent to office, running under floor covering. 2.) under desk in office. 3.) in main lobby under electric sign. 4.) in lobby, ext. cord running through ceiling. |
07/03/2006 | VIOL - MEANS OF EGRESS | DRAMIREZ | Approved | TFC 1008.1.8.4 Flush bolts. Mannually operated flush bolts or surface bolts are not permitted. The flush bolt latches provided for both rear exit doors shall be removed. |
07/03/2006 | VIOL - MEANS OF EGRESS | DRAMIREZ | Approved | TFC 1027.6 Panic hardware. Where panic hardware is installed, whether required or not, panic hardware shall be the only locking device on the door. You shall remove the secondary locking devices from the east main enterance door and from then the southeast rear exit door. |
07/03/2006 | VIOL - MEANS OF EGRESS | DRAMIREZ | Approved | TFC 1008.1.8 Egress doors. You shall provide the west front exit door with a thumb-turning device or with panic hardware. |