Case: T06FR02068
Case Details
Entered Date:
06/23/2006
Applicant:
PERGOM LLC
Description:
Fire Inspection
Outstanding Inspections
Case Number: T06FR02068
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 4
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| INSP - FULL | None | Not Inspected | ||
| 06/23/2006 | VIOL - EMERGENCY PLAN/PREPARE | KFOSTER | Correction Required | TFC-408.11.2 Tenant Spaces. 1) Place Bus. name or suite numbers on exterior side of door in hallway. |
| 06/23/2006 | VIOL - BUILDING SVCS & SYSTEMS | KFOSTER | Correction Required | TFC-605.5 Extension Cords. 2) Remove orange extension cord running through front clerks desk, and brown extension cord running over door way. |
| 06/23/2006 | VIOL - WELDING & OTHER HOT WRK | KFOSTER | Correction Required | TFC-2604.2.6 Fire Extinguishers. 4) Install in a permanent location (1) 2-A : 20-B:C rated extinguisher to be with in 30 ft. of work area. |