Case: T06FR01973
Case Details
Entered Date:
06/13/2006
Applicant:
2004 WAKIMOTO FAMILY LTD PRTNRSHP (THE)
Description:
Full Inspection
Outstanding Inspections
Case Number: T06FR01973
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 9
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/13/2006 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.3 Storage in electrical equipment room |
| 06/13/2006 | VIOL - FIRE RESIST.RATED CONST | TKNAPP | Correction Required | 703.1 Missing ceiling tile in electrical room |
| 06/13/2006 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 901.6 Portable fire extinguishers not inspected (X4) |
| 06/13/2006 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 904.11 Equipment hanging on hood system piping |
| 06/13/2006 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 904.11.5 "K" class extinguisher needed |
| 06/13/2006 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 904.11.6.2 Grease filters not in place |
| 06/13/2006 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 904.11.6.4 Hood system needs to be serviced |
| 06/13/2006 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1026.3 Exit signs throughout not lit |
| 06/13/2006 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1026.5 Emergency illumination light at north side of kitchen O/S |
Completed Inspections
Case Status: COMPLETE
Case Number: T06FR01973
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/15/2006 | INSP - FULL | TKNAPP | Approved |